Zadzwoń do nas: (+48) 33 817 45 98 wew. 37
CHŁODNICA POWIETRZA TEF62L 3,6 kW TIANYICOOL
rozstaw lamel: 6mm z grzałkami elektrycznymi | |||||||||||
TYP | MOC CHŁODNICZA | POWIERZCHNIA | POJEMNOŚĆ WĘŻOWNICY [dm3] | WYDATEK POWIETRZA [m3/h] | WYRZUT POWIETRZA | MOC GRZAŁEK ODSZRANIANIA | PRZYŁĄCZA | ||||
R404a | WYMIANY | [m] | [kW] | ||||||||
[kW] | [m2] | ||||||||||
temp. parowania | |||||||||||
-25℃ | CIECZ | GAZ | ODŁYW | ||||||||
TEF62L | 3,6 | 16,4 | 5,3 | 2260 | 11 | 2,2 | 1/2’’ | 7/8’’ | 1’’ |
WENTYLATORY | |||||||||||
TYP | ILOŚĆ x ŚREDNICA [mm] | PRĘDKOŚĆ OBROTOWA [r/min] | POBÓR PRĄDU [A] | MOC [W] | NAPIĘCIE ELEKTRYCZNE [V/Hz] | ||||||
TEF62L | 2x300 | 1380 | 0,43 | 2x90 | 220v/50Hz |
WYMIARY [mm] | |||||||||||
TYP | H | B | T | L | E1 | F | C | ||||
TEF62L | 264 | 1481 | 607,5 | 644,5 | 1254 | 113,5 | 120,5 |
TEF62L | T.room | -25℃ | -20℃ | -18℃ | -15℃ | -10℃ | -5℃ | 0℃ | 5℃ |
△T 10 (watt) | 4536 | 4716 | 4806 | 4896 | 5076 | 5256 | 5436 | 6066 | |
△T 9 (watt) | 4162 | 4326 | 4410 | 4491 | 4656 | 4821 | 4986 | 5656 | |
△T 8 (watt) | 3787 | 3937 | 4010 | 4087 | 4236 | 4386 | 4536 | 5148 | |
△T 7 (watt) | 3413 | 3547 | 3600 | 3682 | 3817 | 3951 | 4086 | 4662 | |
△T 6 (watt) | 3085 | 3195 | 3251 | 3306 | 3416 | 3526 | 3636 | 4176 |
H-TEF062L-recznie